SPECIFICATION FOR COLD CATHODE LIGHTING SYSTEM
HPB-1
120V
Per ANSI / IES RP-16-10 / IFAY Listed
GALLERY
COLOR CHART
Power Supply:
To be 200MA, High Power Factor, Non-Dimmed, operating at 200MA on T8 (one inch diameter) long life cold cathode lamps. Each power supply to be encapsulated within an approved enclosure and remoted up to 75’ away in an accessible and ventilated location (not exceeding 100° F ambient).
Lamp Holders:
To be “RB”, “RRB”, “CIB” or “SE” series per the specifier. Provide right-angle electrodes or staggered straight electrodes for a continuous line of light, with lamp supports for all curved and bent lamps. Circuit interrupting lampholders must be used per the N.E.C. where applicable.
Lamps:
Shall be 25MM Diameter, closed-loop, lead free and triphosphor coated. (680 Lumens Per Foot).
Cable / Conduit:
1,000V wire will be supplied by N.C.C. and installed by the installing contractor per N.C.C. submitted C.A.D. drawings. Conduit is to be supplied by the installing contractor.
Note: U.L., N.E.C. and the N.B.C. will not accept any cold cathode system with exposed PVC Cable when used adjacent to air handling vents in the coves.
Shop Drawings:
Shall be CAD generated and be submitted for approval and future maintenance. Drawings shall show lighting layout, method of installation, and a complete bill of materials. Installing contractor is responsible for furnishing “As Built” dimensions or full-sized patterns, as requested on shop drawings. This lighting system must comply with ANSI / IES RP-16-10 and U.L. IFAY or be rejected.
Manufacturer:
National Cathode Corp., 269 Essex Street, Hackensack, NJ 07601
Build a Cold Cathode System
Visual Application HPB-1
Using chart below pull-down fields to fill in specs or type in information